4600 Series Electrified Concealed Vertical Rod

4600 Electrified CVR

To order, please click here to be redirected to the product page and choose the electrified option required from the menu.

ADA Compliant: True
BHMA Certified: True
UL C/US Listed: True
Contact Hager for Price

Specifications

Applications

Heavy Duty Commercial

Certifications
  • ANSI/BHMA A156.3-2014 Grade 1
  • UL305 Listed for Panic Hardware
  • UL/cUL Listed for up to 3 hours for "A" labeled doors
  • UL10C Positive Pressure Rated
  • UL10B Neutral Pressure Rated
  • Complies with ANSI 117.1 for accessible buildings and facilities
Cover

Stainless steel, zinc

Cover Tube
Aluminum
Door Thickness

1-3/4" (44 mm) - Standard

Door Width
  • 36” (914 mm) field sizeable to 30” (762 mm) for devices with any monitoring switches.
  • 48” (1219 mm) field sizeable to 36” (914 mm) door for devices with any monitoring switches
  • 36” (914mm) field sizeable to 34” (864mm) door minimum for devices with motorized electric latch retraction
  • 36” (914mm) door minimum for devices with delayed egress
  • 48” (1219mm) field sizeable to 40” (1016mm) door minimum for devices with motorized electric latch retraction
  • 48" (1219mm) door minimum for devices with delayed egress
Electric Modifications
  • RX - Request to Exit
  • RX2 - Dual Request to Exit
  • MLR - Motor Driven Electric Latch Retraction
  • MLRX- Motor Driven Electric Latch Retraction with Request to Exit
  • DE - Delayed Egress
Electrical Specifications
  • RX; 3A @125VAC; 2A @ 30 VDC
  • MLR; 1A inrush @24VDC
  • DE; 430mA @ 24VDC signal; 680mA @24VDC Tandem
End Caps

Standard Flush End Cap (Zinc)

Fasteners
  • Wood and machine screws
  • Thru-bolts
Latchbolt Type
  • Top - 1/2" (13 mm) throw, stainless steel
  • Bottom - 1/2" (13 mm) throw, held retracted during door swing, stainless steel
Maximum Door Height
  • 7' (2134mm) - Standard
  • 8' (2438mm) - Optional
Notes
  • Center line prep is 40". If door prep elevation is lower, a longer rod will need to be ordered
  • Recommended to be used on appropriately reinforced doors
Trim
  • Escutcheon trim
  • Rim cylinder x optional pull
Warranty
  • One year on electrified components
  • Lifetime on hardware components
Wire Requirements
  • Status switches (i.e. RX, LM, etc.) require 2 wires per switch to monitor a normally open (NO) or normally closed (NC) position
  • All devices provide 3 wires per switch so both NO and NC positions can be monitored
  • Monitoring both positions will require 3 wires per switch
Projection
  • 3" (76mm) in undogged position
  • 2-5/8" (67mm) in electrically dogged position
Rod Length
  • Rods for 7' (2134mm) door - Standard
  • Rods for 8' (2438mm) and 10' (3048mm) doors - Optional
  • Door height of 7' (2134mm) requires 33-1/2" (851mm) top rod length
  • Door height of 8' (2438mm) requires 45-1/2" (1156mm) top rod length
Stile Width
  • 2-1/8" (114mm)
  • All stile widths are measure from the door edge